Patterson-Kelley Solutions Blog

Properly Sizing a Buffer / Swing Tank for a Commercial Heat Pump System

[fa icon="calendar"] Mar 17, 2025 11:00:00 AM / by Patterson-Kelley

Patterson-Kelley

 

When designing commercial HVAC systems, proper sizing of a buffer or swing tank is critical for efficient operation, especially in heat pump systems. Buffer tanks—also known as swing tanks—serve as a thermal energy storage solution, ensuring system stability, reducing short cycling, and improving the overall lifespan of heat pumps. These tanks store excess thermal energy when the system output exceeds demand and release it when demand spikes, allowing the system to operate more consistently. Understanding how to properly size these tanks is essential, whether pairing a heat pump with a traditional gas boiler to create a hybrid system or operating the heat pump as a standalone unit.

The Role of a Buffer/Swing Tank in a Heat Pump System

Buffer tanks are designed to decouple the heating system from its load, helping to stabilize temperatures and flow rates. In a heat pump system, this is particularly important because heat pumps function best under steady-state conditions. Frequent on-off cycling can reduce their efficiency, increase wear and tear, and lead to premature failure. By adding a buffer tank, you can smooth out these fluctuations, allowing the heat pump to run longer and more efficiently, even when building demand fluctuates.

In a hybrid system, where a heat pump is paired with a gas boiler, the buffer tank also helps manage the interaction between the two heat sources. It ensures that each source operates optimally and avoids unnecessary cycling, especially during low-demand periods.

 

Key Factors in Sizing a Buffer/Swing Tank

There are several key factors to consider when sizing a buffer or swing tank for a commercial heat pump system:

  1. System Load and Capacity

The first step in sizing a buffer tank is understanding the heating and cooling load of the building and the capacity of the heat pump. The goal is to store enough energy to prevent short cycling, but not so much that the system becomes oversized. The tank must be sized to handle the system's minimum load while allowing the heat pump to operate efficiently during low-load periods.

 

  1. Flow Rate and System Volume

The size of the buffer tank is closely tied to the system’s flow rate and total system volume. Typically, the buffer tank should hold enough water to allow the system to run for a certain amount of time before the heat pump needs to turn on again. This time—often referred to as “off-cycle time”—can vary depending on the type of heat pump, but it generally ranges from 5 to 10 minutes. The flow rate through the system will also impact the required tank volume. For example, systems with higher flow rates will need larger tanks to ensure that adequate water is available for smoothing temperature fluctuations.

 

  1. Temperature Delta (ΔT)

The temperature delta (ΔT) is the difference between the supply and return water temperatures. This temperature difference plays a crucial role in determining how much energy the buffer tank can store. A higher ΔT allows for more energy storage in the same volume of water, reducing the size of the tank required. For example, a ΔT of 10°C will store twice as much energy as a ΔT of 5°C for the same tank volume.

 

  1. Compressor Cycle Times and Minimum Run Times

    Heat pump compressors are designed to run for a minimum period to avoid damage. If the system demand is too low, the heat pump could short-cycle, leading to reduced efficiency and potential equipment failure. The buffer tank provides the extra thermal capacity needed to ensure that the heat pump runs for at least the minimum required cycle time.

  2. Heat Pump vs. Hybrid System Considerations

In a hybrid system with a gas boiler, the buffer tank needs to accommodate not only the heat pump but also the gas boiler's operating characteristics. Boilers typically have different cycling requirements than heat pumps, and the buffer tank helps to balance these two sources of heat. For example, the buffer tank can store excess heat generated by the gas boiler during high-demand periods and release it when demand drops, reducing the need for frequent on-off cycling.

In standalone heat pump systems, the buffer tank primarily serves to smooth out temperature and flow fluctuations, but in hybrid systems, it also acts as a mediator between the two heat sources. Therefore, sizing considerations may differ slightly depending on whether you're designing for a standalone or hybrid setup.

General Sizing Guidelines

While there is no one-size-fits-all approach, a typical rule of thumb is to size the buffer tank based on the system’s flow rate and temperature delta. A good starting point is to aim for 2-5 gallons of buffer capacity per ton of heat pump capacity. For example, a 10-ton heat pump system would typically require a buffer tank in the range of 20 to 50 gallons, depending on the specific system conditions.

However, more complex systems—especially hybrid systems—may require larger buffer tanks to ensure optimal performance. In those cases, consulting with a system designer or using specialized sizing software can help achieve the most accurate result.

Conclusion

Properly sizing a buffer/swing tank for a commercial heat pump system is crucial for ensuring efficient, reliable operation. By considering factors such as system load, flow rate, temperature delta, and compressor cycle times, you can optimize the performance of both standalone and hybrid heat pump systems. The buffer tank not only helps reduce short cycling and wear on equipment but also ensures that the system can respond smoothly to fluctuations in building demand, resulting in a more consistent and energy-efficient operation.

Patterson-Kelley

Written by Patterson-Kelley

Located in East Stroudsburg, Pennsylvania, Patterson-Kelley is a recognized market leader and major producer of heat transfer equipment. Our hydronic boilers and water heaters are installed in institutional, commercial, and industrial building applications such as schools, offices, apartment buildings, dormitories, hospitals, and hotels.